Customized load bank

Custom AC and DC Load Banks Built Around Your Testing Needs

Customized load banks are engineered to match the exact demands of each application. Available in both AC and DC configurations, they deliver dependable performance for diverse testing environments and can be reconfigured whenever your operational requirements evolve.

600 kW Trolley-Mounted Resistive Load Bank

Designed for mobile generator load testing, this manually controlled load bank has 656 kW of installed capacity at 430 V AC, providing 56 kW of reserve above the 600 kW requirement at that voltage. Available resistive load is approximately 568 kW at 400 V.

600 kW trolley-mounted load bank technical specifications
Electrical supply400–430 V AC, three-phase, four-wire balanced load, 50 Hz, unity power factor
Full-load line currentApproximately 881 A at 656 kW and 430 V, excluding auxiliaries
Load control18 manually selected steps with 1 kW nominal resolution, digital electrical monitoring, and LED status indication
Cooling and dutyForced-air cooling with heavy-duty fans, designed for 24-hour continuous operation
ConstructionPowder-coated steel enclosure on a trolley with a towing hook and bearing-type wheels, plus a separate control panel
Dimensions1,200 × 1,800 × 1,200 mm (±100 mm)
ProtectionUnder- and over-voltage, over-current, short circuit, over-temperature warning and trip, fan interlock, airflow failure, and emergency stop
WarrantyOne year

Manual Load Steps

Select from 18 individual steps rated at 430 V: 1, 1, 2, 2, 5, 5, 10, 10, 10, 20, 20, 20, 50, 50, 50, 100, 100, and 200 kW. The combined installed load is 656 kW. Resistive load varies with the square of the applied voltage.

Construction and Site Mobility

The heating elements use Kanthal Grade D resistance material, stainless steel outer sheaths, Grade 3 magnesium oxide insulation, and brass terminal hardware. The enclosed trolley has bearing-type wheels at least 18 inches in diameter and a towing hook. Access panels allow inspection and servicing.

Operating and Design Conditions

  • Ambient temperature up to 55 °C and humidity up to 100%.
  • Full-load temperature-rise requirement of 50 °C above ambient.
  • Class F insulation and a 2.5 kV dielectric test requirement.
  • Service-life design target of 15 years or more.